Share  
Print  
LITTELFUSE

Littelfuse FLSR Series, 10A RK5 Fuse; 5 in. x 13/16 in. dia.

Hover over image to magnify
Fuse,Class RK5,10A,Flsr Series
Fuse,Class RK5,10A,Flsr Series

#935396-8 | Pkg Qty: 1

$17.85 pkg | $17.85 ea
Fuse Amps : 10A

Drop Ship Item

Shipping to 60045
|

Technical Specifications

Key Specifications
AC Voltage Rating
600 VAC
Indicating / Nonindicating
Nonindicating
Body Material
Fiberglass
Interrupt Rating
200kA at 600 VAC, 20kA at 300 VDC
Body Style
Cylindrical
Item
Fuse
Brand
LITTELFUSE
Length
5 in.
Class
RK5
Mfr. Part Number
FLSR010
DC Voltage Rating
300 VDC
Package Quantity
1
Diameter
13/16 in.
Rejection / Nonrejection
Rejection
Element
Dual
Series
FLSR
Functionally Equal To
Bussmann FRS-R, Edison ECSR, Mersen/Ferraz Shawmut TRS-R
Shipping Weight
.17 lb.
Fuse Amps
10A
Speed
Time Delay
General
Compatible Fuse Block Series
LFR
Fuse Size
5 in L x 13/16 in dia
Equivalent Series
ECSR, FLSR, FRS-R, TRS-R
Standards
CE, CSA Certification, QPL-W-F-1814, UL 248-12 Class RK5
Fits Fuse Block Style
Rejection
Visual Indication
Nonindicating

Product Description

These 600VAC UL Class RK5 fuses are time delay and nonindicating. They tolerate temporary inrush currents without opening, which prevents nuisance-blowing from motor and equipment startups. Also called slow-blow Class RK5 fuses, these 200kA IR fuses open to disconnect an electrical circuit when exposed to sustained loads and short circuits. They have no indicator for identifying a blown fuse, so they're sometimes used with an indicating fuse block or cover.

UL Class RK5 fuses provide moderate current limitation for general use applications where more current-limiting RK1 fuses aren't needed. These fuses have an interrupting rating (IR) of 200kA and are the same size as Class H and K fuses, but have a rejection feature that prevents an accidental downgrade from a current-limiting system. Their modified terminals ensure a match with the rejection clips in Class R fuse holders that prevent the installation of fuses with a lower interrupting capacity. They're typically used in newer equipment, but can also be used with a Class H fuse holder to upgrade older installations from Class H or K fuses for improved overcurrent protection. They are current-limiting to prevent electrical damage by disconnecting circuits before they're exposed to the full magnitude and duration of an overcurrent.

Compliance & Restrictions

California Proposition 65 Icon
WARNING: This product can expose you to chemicals including Lead, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov.
Item Barcode
9353968
Fuse,Class RK5,10A,Flsr Series
 NameItemDescription
Grainger DropshipGrainger Dropship486L27
UNSPSC CODESUNSPSC CODES39121604
VMRS (ATA) CODESVMRS (ATA) CODES053-006-009Fuse,Class RK5,10A,FLSR

For more product information by email, click here